AWG, Metric Wire Size and Circular Mils Reference

AWG lookup tables and definitions for solid-wire diameter, metric cross-sectional area, circular mils, kcmil, gauge notation, and geometry conversion boundaries.

Reading Time
13 min
AWG Range
4/0 to AWG 40
Updated
September 27, 2026

AWG Diameter and Area Lookup

Values are formula-derived bare solid-conductor geometry. Display rounding does not replace the full-precision shared data used by calculators.

AWG diameter and area lookup
GaugeDiameter mmDiameter milArea mm²Circular milkcmil
4/011.6840460.000107.2193211600211.6000
3/010.4049409.64285.0288167806167.8064
2/09.2658364.79767.4309133077133.0765
1/08.2515324.86153.4751105535105.5345
AWG 26.5437257.62633.63086637166.3713
AWG 45.1894204.30721.15064174141.7413
AWG 64.1154162.02313.30182625126.2514
AWG 83.2636128.4908.36561651016.5097
AWG 102.5882101.8975.26121038310.3830
AWG 122.052580.8083.308865306.5299
AWG 141.627764.0842.080941074.1067
AWG 161.290850.8211.308725832.5827
AWG 181.023740.3030.823016241.6243
AWG 200.811831.9610.517610221.0215
AWG 220.643825.3470.32556420.6424
AWG 240.510620.1010.20474040.4040
AWG 260.404915.9410.12882540.2541
AWG 280.321112.6410.08101600.1598
AWG 300.254610.0250.05091010.1005
AWG 320.20197.9500.0320630.0632
AWG 340.16016.3050.0201400.0398
AWG 360.12705.0000.0127250.0250
AWG 380.10073.9650.0080160.0157
AWG 400.07993.1450.0050100.0099

Geometry and Gauge Relationships

Wire geometry relationships
QuantityRelationshipBoundary
AWG diameterd(in) = 0.005 × 92^((36 − AWG)/39)Formula for AWG solid-conductor nominal diameter
Metric areaA = πd²/4Round solid metallic conductor
Mil1 mil = 0.001 in = 0.0254 mmDiameter unit, not area
Circular milcmil = d(mil)²Defined circular-area unit
kcmil1 kcmil = 1000 cmilLarge conductor area
Area conversion1 cmil = π/4 × (0.001 in)²Converts circular mil to ordinary square area
Gauge stepSix AWG steps double diameter approximatelyArea changes by about four times
Stranded areaAmetal = Σ(πdstrand²/4)Overall bundle diameter also depends on lay and packing

Common Cross-Checks

AWG cross-checks
ReferenceApproximate valueUse
AWG 102.588 mm diameter; 5.261 mm²Common geometry anchor
AWG 122.053 mm diameter; 3.309 mm²Compare with nearby metric preferred sizes
AWG 181.024 mm diameter; 0.823 mm²Harness and low-power geometry anchor
AWG 240.511 mm diameter; 0.205 mm²Signal-wire geometry anchor
AWG 300.255 mm diameter; 0.0509 mm²Fine-wire geometry anchor
1 mm²≈1973.5 cmilArea conversion only; not an AWG designation

Common Wire-Size Mistakes

  • Assuming a larger AWG number means a larger conductor.
  • Treating an AWG-to-mm² conversion as a preferred metric size designation.
  • Confusing diameter in mils with area in circular mils.
  • Using kcmil as a diameter unit.
  • Using bare solid diameter as insulated cable outside diameter.
  • Treating stranded bundle diameter as equivalent solid diameter.
  • Confusing AWG with SWG or another gauge system.
  • Rounding diameter before calculating area.
  • Using conductor area alone to claim ampacity.
  • Ignoring material when estimating resistance or mass.
  • Ignoring installation and temperature limits.
  • Using display-rounded table values for precision round trips.

Support reference

FAQ

What does AWG mean?

American Wire Gauge is a logarithmic solid-conductor diameter system. Larger gauge numbers represent smaller diameters.

Why does a lower AWG number mean a larger wire?

The historical gauge sequence is inverse: each step toward a smaller number increases diameter by a fixed geometric ratio.

What are 1/0, 2/0, 3/0, and 4/0 AWG?

They are progressively larger sizes below AWG 1, also written 0, 00, 000, and 0000.

Is AWG area the same as metric nominal wire size?

No. An AWG cross-sectional area can be converted to mm², but standard metric nominal sizes are separate preferred values.

What is a circular mil?

A circular mil is the area of a circle one mil in diameter. Numerically, circular-mil area equals diameter in mils squared.

What is kcmil?

One kcmil is 1000 circular mils. It is commonly used for large conductor areas.

Does strand count change conductor area?

A stranded conductor's metallic area is the sum of strand areas. Its overall outside diameter is larger because strands do not pack without voids and insulation adds thickness.

Can wire diameter determine ampacity?

No. Ampacity depends on material, insulation, temperature rating, installation, bundling, airflow, allowable rise, and applicable rules.

Does this table include insulation diameter?

No. The values describe ideal bare-conductor geometry; insulation and construction dimensions come from the cable datasheet.

Are AWG and SWG interchangeable?

No. American Wire Gauge and Standard Wire Gauge use different diameter sequences.

How is area calculated from diameter?

For a round solid conductor, A = πd²/4. Circular-mil area uses d² when d is expressed in mils.

Why can published AWG tables differ slightly?

Exact formula values may be rounded to different decimal places, and stranded or finished-wire dimensions may be mistaken for bare solid-conductor diameter.