ECParts Toolkit LogoECParts Toolkit

Wire Size Calculator

Calculate minimum conductor area and recommended AWG based on a DC voltage-drop limit, cable length, load current, supply voltage, and conductor material. Results are voltage-drop sizing estimates only and do not verify ampacity or electrical-code compliance.

Engineering tool

Wire Size Calculator

Find the minimum conductor area and smallest qualifying AWG based only on an entered DC voltage-drop limit. This is not an ampacity or code-compliance calculator.

Voltage drop limit type

Used as the percentage denominator and for estimated load voltage.

Sizing requires current greater than zero.

Physical source-to-load distance. The two-conductor DC loop uses twice this length.

Percentage is based on supply voltage: Vdrop / Vsupply × 100%.

Material presets reuse the WIR-001/WIR-002 shared AWG reference data.

Result console

Minimum Area Based on Voltage-Drop Limit
5.74667mm²
Recommended AWG Based on Voltage-Drop Limit
AWG 9
Predicted Voltage Drop
0.51973V
Predicted Voltage Drop Percentage
4.3311%
Recommended AWG Actual Area
6.63419mm²
Predicted Loop Resistance
0.05197Ω
Estimated Load Voltage
11.48027V
Wire Power Loss
5.19732W
Maximum Allowed Drop
0.6V
Allowed Drop Percentage
5%
One-Way Cable Length
10m
Total Conductor Length
20m
Load Current
10A
Material
Copper
Resistivity
1.724e-8Ω·m

Minimum size is based on the specified voltage-drop limit only. Ampacity, code compliance, insulation rating, installation method, bundling, termination rating, and fault protection are not verified.

Formula reference

Voltage-drop wire sizing formulas

WIR-003 solves the inverse voltage-drop problem and then verifies the selected AWG with the forward WIR-002 voltage-drop model.

Rloop = 2ρL/AVdrop = I × RloopArequired = 2ρLI / Vdrop,maxVdrop,max = Vsupply × p/100%drop = Vdrop/Vsupply × 100%

Variable definitions

ρ
conductor resistivity
L
one-way cable length
I
load current
A
conductor cross-sectional area
p
maximum voltage-drop percentage

WIR-003 Formula Audit

Core Sizing FormulaArequired = 2ρLI / Vdrop,max.
One-Way Length ConventionL is source-to-load one-way cable length.
Total Conductor Length ConventionLtotal = 2 × Lone-way for two equal DC conductors.
Percentage Drop Formula%drop = Vdrop / Vsupply × 100%.
Allowed Drop ConversionVdrop,max = Vsupply × p / 100 in percentage mode.
Required Area FormulaArequired uses the complete two-conductor loop relation Rloop = 2ρL/A.
AWG Selection RuleSelect the smallest conductor whose raw AWG area is greater than or equal to required area.
AWG DirectionLarger AWG number means smaller conductor area.
AWG Precision PolicySelection uses raw shared dataset values, not rounded display values.
Post-Selection VerificationSelected AWG is forward-calculated with WIR-002 to verify voltage drop.
AWG Out-of-Range HandlingNo AWG is returned if the required area exceeds the supported dataset.
Material Data ReuseCopper/aluminum presets reuse WIR-001 material data.
Reference Temperature PolicyPreset resistivity values are approximate reference values near 20°C.
Temperature BoundaryNo full conductor temperature correction.
DC / AC BoundaryDC and low-frequency resistive sizing only.
Three-Phase BoundaryNo partial √3 three-phase shortcut.
Ampacity BoundaryNo current capacity, fuse, breaker, or thermal approval.
Code Compliance BoundaryNo NEC, IEC, UL, CSA, or local-code compliance result.
WIR-002 BoundaryWIR-002 forward-calculates voltage drop for known wire.
WIR-004 BoundaryWIR-004 will solve maximum cable length; WIR-003 does not.

Worked Examples

CaseCalculationResult
Critical area2 × 1.724e-8 × 10m × 10A / 0.5V6.896mm²
12V at 5%Vdrop,max=0.6V5.74667mm²
24V at 5%Vdrop,max=1.2V2.87333mm²
Percentage conversion12V × 5 / 1000.6V
Exact round tripArequired into WIR-002recovers allowed drop
AWG selectionraw AWG area ≥ required areasmallest qualifying conductor
Next thinner checknext smaller areafails requirement when present
Total lengthone-way 10m20m conductor path
Double currentI ×2Arequired ×2
Double lengthL ×2Arequired ×2
Double resistivityρ ×2Arequired ×2
Double drop limitVdrop,max ×2Arequired ÷2
Higher supply at same %24V vs 12Vsmaller required area
Higher percentage10% vs 5%smaller required area
Copper vs aluminumsame geometryaluminum requires more area
mV conversion1mV0.001V
mA conversion1mA0.001A
ft conversion1ft0.3048m
in conversion1in0.0254m
mm² conversion1mm²1e-6m²
Ω·mm²/m conversion1Ω·mm²/m1e-6Ωm
µΩ·cm conversion1µΩ·cm1e-8Ωm
Zero currentI=0rejected for sizing
Zero lengthL=0rejected for sizing
Out of rangerequired area beyond AWG tableexact area retained, no undersized AWG

Engineering Notes

  • WIR-003 sizes conductors from a voltage-drop requirement only.
  • The primary result is minimum conductor area, not a universal safe wire size.
  • Recommended AWG is selected from raw shared AWG area data.
  • AWG numbers run backward: smaller numbers are larger conductors.
  • One-way length is doubled internally for the two-conductor DC loop.
  • Copper and aluminum resistivity values come from shared material data.
  • Reference resistivity is not the same as hot conductor resistance.
  • Allowed voltage-drop percentage is based on supply voltage.
  • Higher current or longer cable requires larger conductor area.
  • Higher supply voltage allows more absolute drop for the same percentage limit.
  • The calculator does not check ampacity, breaker size, fuse size, or code compliance.
  • Insulation rating, ambient temperature, bundling, and installation method still matter.
  • Termination ratings and fault protection must be checked separately.
  • Complete AC or three-phase cable sizing is outside WIR-003.

Common Mistakes

  • Treating the result as ampacity approval.
  • Forgetting the return conductor.
  • Entering total loop length as one-way length.
  • Doubling length twice.
  • Entering 5% as 0.05 when the field expects percent.
  • Using load voltage as the percentage denominator.
  • Selecting an AWG smaller than the required area.
  • Misunderstanding AWG number direction.
  • Using rounded AWG area instead of raw data.
  • Using cable outside diameter as conductor area.
  • Assuming copper and aluminum have the same resistivity.
  • Ignoring conductor temperature.
  • Using DC sizing as a complete AC cable design.
  • Assuming 3% or 5% is universal for every system.

Support reference

FAQ

How do I calculate required wire size?

For a two-conductor DC cable, use Arequired = 2ρLI / Vdrop,max, where L is one-way cable length, I is load current, ρ is resistivity, and Vdrop,max is the allowed voltage drop.

How do I size wire for voltage drop?

Choose the maximum allowed voltage drop, calculate the minimum conductor area, then select the smallest available AWG conductor whose raw area is greater than or equal to that requirement.

What is the wire size formula?

The voltage-drop sizing formula is Arequired = 2ρLI / Vdrop,max for a two-wire DC loop using one-way source-to-load cable length.

How do I calculate required conductor area?

Convert all inputs to SI units, calculate the maximum allowed voltage drop, then divide 2ρLI by that drop limit.

How do I choose AWG from required area?

Compare the calculated required area against the shared AWG dataset and choose the smallest conductor whose raw area is not smaller than the requirement.

Does a larger AWG number mean a larger wire?

No. AWG is reversed: larger gauge numbers usually mean smaller conductor area and higher resistance.

Why is cable length doubled?

Current flows through the outgoing conductor and returns through another conductor, so the total conductor length is twice the one-way physical cable run.

What does one-way cable length mean?

One-way cable length is the physical distance from source to load. The calculator reports total conductor length separately.

How does current affect required wire size?

Required conductor area is directly proportional to current. Doubling current doubles the required area for the same drop limit.

How does cable length affect required wire size?

Required conductor area is directly proportional to one-way cable length. Longer cable runs need more conductor area for the same voltage-drop limit.

How does supply voltage affect wire size?

In percentage mode, higher supply voltage allows a larger absolute drop for the same percentage limit, so required area decreases.

How does allowed voltage drop affect wire size?

Required area is inversely proportional to the allowed voltage drop. A stricter drop limit requires a larger conductor.

How do I size wire using a percentage voltage drop?

The calculator converts the percentage to voltage using Vdrop,max = Vsupply × percentage / 100, then applies the conductor sizing formula.

Is voltage drop percentage based on supply voltage?

Yes. It is based on supply voltage, matching WIR-002: %drop = Vdrop / Vsupply × 100%.

Can I size copper wire?

Yes. Copper is available from the shared AWG material dataset and is the default material preset.

Can I size aluminum wire?

Yes. Aluminum is available as a shared material preset and generally requires more area than copper for the same drop limit.

Does wire temperature affect the result?

Yes. Conductor resistance changes with temperature. This calculator uses reference resistivity and does not perform full temperature correction.

Does this calculator account for conductor temperature?

No. Full conductor temperature correction belongs to WIR-011. Use margin or measured hot resistance for critical wiring.

Does this calculator check ampacity?

No. It only checks the entered voltage-drop criterion and does not verify thermal current capacity.

Is the recommended AWG NEC compliant?

No NEC compliance is implied. The recommendation is only based on the entered voltage-drop limit and shared AWG area data.

Is the recommended AWG IEC compliant?

No IEC compliance is implied. Verify final conductor selection against applicable standards and installation requirements.

Is 3% voltage drop always required?

No. Acceptable voltage drop depends on the system, load tolerance, regulation budget, and applicable standards.

Can I use this calculator for AC circuits?

Only as a simple low-frequency resistive estimate. Complete AC sizing may need reactance, power factor, skin effect, and proximity effect.

Can I use this calculator for three-phase circuits?

No. WIR-003 does not provide a complete three-phase cable sizing model.

What happens if the required area is larger than the supported AWG range?

The calculator keeps the exact required area and shows an out-of-range warning instead of returning an undersized AWG.

Wire Resistance Calculator

Available

Calculate conductor resistance from material, length, area, and AWG.

Open calculator

Wire Voltage Drop Calculator

Available

Forward-calculate voltage drop for a known conductor and current.

Open calculator

AWG to mm² Converter

Available

Convert AWG to diameter, area, circular mils, and reference values.

Open calculator

Power Dissipation Calculator

Available

Calculate I²R loss once current and resistance are known.

Open calculator

Documentation

Guides and lookup references linked to this tool.